CONTRACT/PROJECT SPECIFICATION
Specific Requirement:
100 mm dial White with Black numerals. Industrial Type, Min. 316 SS, Bourdon Tube for High Pressure, Diaphragm for Corrosive action. Micrometer adjustable pointer Epoxy Coated. 1.5 times over pressure protection, SS 304 casing, Process connection DN15 NPT(M), IPW-55, Glycerin filled gauges for vibration area.
Type: Direct
Technical Spec:
Accuracy ± 1.5% of Full scale

ACTUAL CONDITIONS
Datasheet
KKS No. 31/32LAB95CP501, Operating Condition: Temp: 155.79/374 °C|Pressure 143.55/220 Bar(g)|Flow: 190.62/190.872 t/h| Range:0-300 Bar(g)|Maker: WISE
Application: HP Feed Water Line (After Check Valve)
Parameter: Pressure, Medium: Water, Max Pressure: 220 Bar(g)
Type of sensor: (PI) Bourdon
CALIBRATION DATA
Inspection date: Dec 19, 2017
Calibrator:
Hand Held Test Pump | SIKA | SN.043170 | Exp. Date: May 9, 2018
Range: 0~300 Bar
Results:
| Note: | HRSG | |||||||
| No. | KKS No. | Range | Input | 0 | 50 | Error | 100 | Error |
| 1 | 31LAB95CP501 | 0 - 300 Bar | Increase | 0 | 150 | - | 300 | - |
| 32LAB95CP501 | Decrease | 0 | 150 | - | 300 | - |
Conclusion: The affected pressure gauge/indicator is accepted
Tidak ada komentar: